Application of Semi-Empirical Ventilation Models in A Mediterranean Greenhouse with Opposing Thermal and Wind Effects. Use of Non-Constant Cd (Pressure Drop Coefficient Through the Vents) and Cw (Wind Effect Coefficient)
Identifiers
Share
Metadata
Show full item recordAuthor/s
López Martínez, Alejandro; Molina Aiz, Francisco Domingo; Valera Martínez, Diego Luis; López Martínez, Javier; Peña Fernández, Ana Araceli; [et al.]Date
2019-11-10Abstract
The present work analyses the natural ventilation of a multi-span greenhouse with one roof vent and two side vents by means of sonic anemometry. Opening the roof vent to windward, one side vent to leeward, and the other side vents to windward (this last vent obstructed by another greenhouse), causes opposing thermal GT (m3 s−1) and wind effects Gw (m3 s−1), as outside air entering the greenhouse through the roof vent circulates downward, contrary to natural convection due to the thermal effect. In our case, the ventilation rate RM (h−1) in a naturally ventilated greenhouse fits a second order polynomial with wind velocity uo (RM = 0.37 uo2 + 0.03 uo + 0.75; R2 = 0.99). The opposing wind and thermal effects mean that ventilation models based on Bernoulli’s equation must be modified in order to add or subtract their effects accordingly—Model 1, in which the flow is driven by the sum of two independent pressure fields GM1=√(∣∣G2T±G2w∣∣) , or Model 2, in which the flow is driven by the sum...
Palabra/s clave
greenhouse
natural ventilation
sonic anemometry
ventilation model